80-750kVA
The G9000 series UPS is available in capacities of 80, 100, 160, 225, 300, 500, and 750 KVA and comes with an industry-leading three-year on site warranty. It is designed for stand-alone operation or as a parallel system with up to four-unit configurations. All without the requirement of special switchgear cabinet.
With Power Factory ratings of 0.9PF for the 80-225kVA size and 1.0PF for the 300-750kVA size the G9000 series has can provide the power that other competitor's units can not provide.
The G9000 Series incorporates the new Toshiba IGBT technology in the UPS. This IGBT technology is used in the rectifier/converter, DC/DC chopper, and the inverter sections of the UPS. By using this new IGBT technology the G9000's double-conversion topology provides an AC/DC/AC efficiency of 96.5% or greater at loads from 50% to 100%. Even at 20% loading, the efficiency remains greater than 94%. This is 10% to 20% better than current industry systems, making the G9000 excellent for N+1 parallel systems where system loads are typically 30-40% of system capacity.
These units will pave for themselves in energy savings in a relative short time as compared to our competitors models.
Click Here for the Full
Brochure. (1MB)
| G9000 Specifications |
| Model Number |
T90S3S08KS6XSN |
T90S3S10KS6XSN |
T90S3S16KS6XSN |
T90S3S22KS6XSN |
| Capacity |
kVA/kW |
80 / 72 |
100 / 90 |
160 / 144 |
225 / 202.5 |
| Topology |
True On-Line, Double Conversion, Advanced Multi-Level IGBT Technology |
| Input |
Voltage |
480 V, Three-Phase, Three-Wire + Ground/Bypass Input, 480 V, Three-Phase, Three-Wire + Ground |
| Voltage Range |
480 V, -20% to +15% (384 to 552 V Without Utilizing Battery) |
| Power Factor |
Greater than 0.99 |
| Current THD |
<3% at 100% Load (No Input Filter Required) |
| Frequency |
60 Hz (± 10%) |
| Current Limit |
125% Max |
| Output |
Voltage / THD |
480 V, Three-Phase, Three-Wire + Ground |
| Frequency |
60 Hz, ±0.01% (In Free-Running Mode) |
| Voltage Regulation |
±1.0% (0.5% Typical) |
| Power Factor |
0.9 Lagging |
| Power Factor Range |
0.9 Lagging to 0.95 Leading |
| Voltage THD |
<2% for Linear Load, <5% for Non-Linear Load |
| Overload (inverter) |
125% for 2 Minutes; 150% for 60 Seconds |
| Overload (bypass) |
1000% for One Cycle |
| Battery |
DC Link |
480 V DC |
| Environment |
Temperature Range |
32° to 104°F (0° to 40°C) |
| Relative Humidity |
5% to 95% Non-Condensing |
| Heat Rejection |
10,771 BTUs/Hour |
13,463 BTUs/Hour |
17,821 BTUs/Hour |
25,060 BTUs/Hour |
| Efficiency (Full Load) |
95.80% |
95.80%
|
96.50% |
96.50% |
| Efficiency (20% Load) |
92.50% |
92.50%
|
94.70% |
94.90% |
| Altitude |
7380 Feet Maximum Without Derating (2250 Meters)
|
| Audible Noise |
70 dBA at 1 Meter |
| Dimensions |
Dimensions (W x D x H) |
27.6 x 32.8 x 80.6 in.
|
35.4 x 32.8 x 80.6 in.
|
| Weight |
855 lbs |
855 lbs |
31160 lbs |
1230 lbs |
| Features |
Digital Signal Processor (DSP) Control, Fully Digital IGBT Converter & Inverter, High Efficiency Over Wide Load Range,
Transformer-Less Design, N+1 and N+N (Up to Four in Parallel) Capability, Dual-Input Feed, Electronic Battery Isolation,
RS232 and Dry Contact Interface, Small Footprint, Lightweight Design |
| Standards |
UL 1778, CUL, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), FCC Class A, Article 47, Part 15.B |
| Warranty |
Three Years Onsite (Optional Two Year Extended Warranty)
See Toshiba Warranty Policy for Full Details |
| Service |
7x24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)
|
|
|