Power Systems Specialists, Inc.
Call Toll Free (888) 305-1555

APC Mitsubishi Toshiba Chloride Datron
UPS Systems G8000 Series 3 Phase
Toshiba G8000 Series 3 Phase UPS

Our G8000 UPS is widely used in the medical industry where power protection is critical.  The G8000 offers unity power factor output which provides 20% more power than other UPS manufacturers.  It is also 100% generator compatible, and its low input current harmonics means that you do not need to oversize your generator! In addition, the G8000's high crest factor is perfect to use on medical equipment such as MRIs and CT Scanners which have a high current inrush.

 

G8000 Specifications
Model Number T80S3K10KK6XSNH T80S3K15KK6XSNH T80S3K22KK6XSNH T80S3K30KK6XSNH
Capacity
kVA/kW
100 / 100
150 / 150
225 / 225
300 / 300
Topology
True on-line, double conversion, IGBT PWM, with input power factor correction and unity power factor on output
Input Voltage
AC Input 480 V 3 Phase, 3 wire + Gnd / Bypass Input 480 V 3 Phase, 4 wire + Gnd
Voltage Range
408 - 528 V (without utilizing battery)
Power Factor
Greater than 0.98
Current THD
5% Max
Frequency
60Hz (+/- 5%)
Current Limit
125% Max
Output Voltage / THD
480 V, 3 Phase, 4 wire + Gnd / 1% THD Typ
Frequency
60Hz +/- 0.01%
Power Factor
1.0 Unity (20% more power)
Voltage Regulation
+/- 0.5%
Overload (inverter)
125% for 10 Min, 150% for 60 sec
Overload (bypass)
1,000% for 1 cycle, 125% continuous
Battery DC Link
360 V DC
Ripple voltage
+/- 0.5%
Environment Temperature Range
0° -30° C Unity PF (Operating) / 0 -40°C .8 PF (Operating) / -20 - 50°C (Storage)
Relative Humidity
30-95% Non-Condensing
Heat Rejection
23,720 BTUs / Hr
32,670 BTUs / Hr
49,000 BTUs / Hr
65,335 BTUs / Hr
Efficiency
93.5%
94%
Dimensions Dimensions (L x W x H)
36.8"L x 31.5"W x 78.7"H
55.1"L x 31.5"W x 78.7"H
76.8"L x 35.4"W x 78.7H"
Weight
2200 lbs
2756 lbs
3307 lbs
4400 lbs
Altitude
6600 ft (2000 m) (Max w/o derating)
Audible Noise
< 65 dBA at 1 meter
< 68 dBA at 1 meter
70 dBA at 1 meter
Features
Output Unity Power Factor, Dual Input Feed, Output Isolation Transformer, RS232 and Dry Contact Interface
Standards
UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587)
Warranty
Three Years on Electronics (UPS) when PM's are purchased / Two years full on Battery (See Toshiba warranty policy for full details)
Service
7x24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)
 

Home | Power Quality Products | Power Quality Services

Send e-mail to: webmaster@p-s-s.com with questions or comments about this web site. Copyright © 2002-2006 Power Systems Specialists, Inc.