Power Systems Specialists, Inc.
Call Toll Free (888) 305-1555

Flooded (Wet) Cell Batteries & Systems Sealed (Valve Regulated) Batteries & Systems
UPS Batteries C&D Wet Cell
C&D Flooded (Wet Cell) Batteries

These batteries are the ideal choice for U.P.S., emergency lighting, switchgear and other standby applications which need reliable, high rate power. Since these batteries are low-gassing they require no special ventilation. Additionally, a compact design makes them perfect for low maintenance and space restricted applications.

 

 

XT Plus

The XT Plus cell combines the features of the XT Series, plus wrapped positive plates for longer cycle life. In heavy cycling applications, positive plate shedding and active material wash-out is the most common failure mode of batteries. C&D has countered this problem by designing the XT Plus, a high-cycling battery with a fiberglass positive wrap, inhibiting shedding and active material wash-out.

  • Available in single, twin, and four cell units
  • Provides .810 to 7.234 kilowatts per cell (15 minute rate to 1.67 volts per cell)
  • Ideal for 100 to 2000 K-VA UPS

XT Antimony

For customers who need a deep cycling battery, C&D offers the XT in a lead-antimony alloys The XT Antimony battery provides lower float voltage requirements over its lead-calcium counterpart.

  • Available in single, twin, and four cell units
  • Provides .81 0 to 7.234 kilowatts per cell

XT Series

A common complaint of antimony batteries is the high maintenance cost associated with frequent watering intervals. The XT Series is constructed of lead-calcium instead of lead-antimony which extends watering intervals without sacrificing performance. This translates into lower maintenance costs and fewer headaches. In addition, the XT features hardened terminals with copper inserts that provide superior conductivity compared to lead alloy posts. The flame-retardant thermoplastic cover meets UL 94-VO fire-retardancy requirements.

  • Available in single, twin, triple, and four cell units
  • Provides .246 to 7.615 kilowatts per cell (15 minute rate to 1.67 volts per cell)
  • Ideal for 50 to 2000 KVA UPS

C&D Battery Cycle Monitor
We have made every attempt to provide accurate and up-to-date information on the C&D Batteries, but for the latest, and most accurate information you should contact C&D directly at http://www.cdpowercom.com/ , or send us email with your specific questions regarding C&D Batteries and we will get the answers for you.

Warranty Information
C&D Cycle Service Warranties.
 
In the past, UPS battery suppliers followed the practices of the telephone industry and only offered 10 to 20 year float warranties. The float service warranties usually had it clause limiting the number of cycles allowed per year. Only after a cell fails do most owners learn that their bat- tery was exposed to "cycle service", invalidating most float warranties. C&D recognizes that UPS batteries are cycled and require cycle warranties. To meet this challenge, C&D has developed a unique Cycle Service Warranty in addition to its standard Float Service Warranty. The Cycle Service Warranty defines the battery life expectancy and refund adjustments in terms of number of cycles for various duration instead of number of years. To assure you are getting the maximum performance from your UPS battery purchase, compare each manufacturers' cycle claims and then ask each manufacturer how they intend to backup and validate their cycle warranty.
 

Home | Power Quality Products | Power Quality Services

Send e-mail to: webmaster@p-s-s.com with questions or comments about this web site. Copyright © 2002-2011 Power Systems Specialists, Inc.