Power Systems Specialists, Inc.
Call Toll Free (888) 305-1555

Sensaphone Custom Systems
Environmental Monitoring
The Sensaphone® SCADA 3000

SCADA groupSCADA 3000: The fully integrated control system. With the SCADA 3000, the high cost of control is history!

SCADA 3000 provides everything you need--from software to modules--in one comprehensive package.

  • Flexible Communication: Use standard data radio, ordinary phone lines, or a mix of both.
  • Built-in Alarm Notification: Alarm reports using custom voice, numeric pager, alphanumeric pager, fax, or E-mail.
  • Built-In Data Logging: Time-stamped data. The SCADA 3000 package includes software for data logging radio network applications, too.
  • Powerful Programming Options: Ladder, C-Programming, PID Functions, and even remote access programming.
  • Flexible Power Sources: with intelligent battery charging, safe battery cut-off and even built-in support for solar power.
  • Live Web Pages: generate reports as web pages on your internet or intranet site, with customizable features and programmable time intervals.

Software

Included in purchase price, the software package provides the capability to program units, develop ladder and C programs, retrieve and analyze data and event logs, and print reports. Automatically polls for data via phone or radio; uses customized screen graphics; provides true 32-bit code for WindowsTM 95, 98, ME, NT and 2000.

Free, powerful 32-bit SCADA software with critical built-in features:

Ladder Editor: the preferred language for control functions. SCADA 3000 supports up to 128 FPU variables and 4096 bits organized as 255 16-bit words. It uses standard Ladder elements and instructions.

Ladder screen

C-Program Editor: for sophisticated control programming, define up to 1024 variables with up to 15 characters per variable name. Run the C program synchronously or asynchronously with the ladder program.
PID Programming: eight built-in programmable PID control algorithms allow the SCADA 3000 to operate as a feedback controller.
Alarm Functions: Alarm up to 64 events from any input, output variable or value that has a UAF. Program recognition time, high and low limits, and reset time. Record custom voice messages for any alarm.
Real Time Screen Builder: Create a custom screen to show the real-time status of I/O values and process variables. Use standard graphical representations of your processes.

RealTime editor
Data Logging: Store up to 50,000 samples from up to 128 I/O points or system variables (UAFs). Date and time stamp. Query multiple units and display the information in grid format.
Communications Manager: Communicate by data radio to keep your PC in constant communication with all connected RTUs, or by phone line if you want to receive information from RTUs on an as-needed basis. Configure up to four serial ports for radio and/or phone communication.


Hardware Configuration
16 Universal Inputs: Contact closures, Thermistors, 4-20mA Analog, 0-5V Analog, Run time accumulator
8 Outputs: Latching 2 amp relays, LED status indicators
2 RS232 Ports: Local programming, Data radio communications; RJ11 Phone interface
LCD: 4x20 character scrolling display; user-customized content for local viewing.

Features
Data Logging: User-programmable, built-in data storage for I/O points or calculated values.
Event Logging: Internal tracking of alarms and events
Ladder Logic Programming: for true PLC-type control; visual ladder editor standard in the software package.
C-Programming: Built-in C-compiler, which can run independent of ladder program.
PID: Eight PID loops built into the internal programming. Any I/O points may be used for PID calculations.
Web Page Generation: Software to upload I/O status and alarm data as a customizable web page to the URL of your choice.
AGA Gas Flow Calculation

Options
Input/Output: expandable to 144 points, with these additional SCADA 3000 Modules:
  • Universal Inputs (identical to the 16 built into the main unit)
  • High Speed Pulse Count Inputs (up to 10kHz)
  • Thermocouple Inputs (Types J, K, R, S, T and E)
  • Relay Outputs
  • Analog Outputs (4-20mA)
  • Annunciator

Communication: Phone modem; voice module.
Power Supply: Hard-wired for 110 or 220 VAC; Plug-in for 110 or 220 VAC; standard or extended battery backup.


Warranty & Compliance
A 3-year comprehensive warranty, and unlimited technical support available by phone, E-mail and internet.
The Sensaphone SCADA 3000 is manufactured in the USA.
 

Home | Power Quality Products | Power Quality Services

Send e-mail to: webmaster@p-s-s.com with questions or comments about this web site. Copyright © 2002-2006 Power Systems Specialists, Inc.