Mitsubishi’s 9800AD Series Uninterruptible Power Supply 100/150/225/300/375/500/750kVA
SINGLE AND MULTI-MODULE SYSTEMS

Mitsubishi 9800 UPSToday's business climate requires UPS Systems that offer not only Reliability but also Flexibility. Mitsubishi Electric Multi-Module Systems (MMS) utilize UPSs with independent parallel control and bypass circuits, and a unique Critical Load Cabinet (CLC) to offer complete System Reliability and Flexibility.

Parallel control circuitry, system static bypass and control circuitry reside in each individual Multi-Module System UPS, optimizing control redundancy and eliminating common control single points of failure. This results in highly reliable system architecture.

For many installations, System Expansion with the addition of UPS modules is required if future load demand becomes apparent. For most MMS available today, the reverse scenario of System Reduction with the capability of utilizing the removed UPS module is not possible without UPS module modification. With the Mitsubishi Electric MMS, not only System Expansion but also System Reduction is possible, with the capability to utilize the removed UPS module for Single Module System (SMS) applications, because each UPS module has independent static bypass and control circuitry. This System Expansion and Reduction results in a highly flexible system configuration.

Download a spec sheet 9800AD Brochure (.pdf)

IGBT - Excellent Performance Characteristics

IGBT Insulated Gate Bipolar TRansistorMitsubishi Electric is the leading manufacturer of Insulated Gate Bipolar Transistors (IGBT). IGBTs are utilized in the 9800AD Series UPS Systems. These advanced, high-performance transistors provide a variety of intelligent features:

  • Large power capabilities
  • High speed switching
  • Low control power consumption

Low Input Current Harmonics (THD)
6% Typical (100% Load)

Heat Loss/High Efficiency
Use of IGBTs for the Inverter permits efficient switching speed (2kHz), thus reducing heat dissipation in the UPS. (Higher efficiency means lower cost per kilowatt to the customer.)

Operator-Friendly Control Panel Features
  • Mimic flow diagram
  • Operator control station
  • Touch panel input

LCD Monitor
  • UPS metering
  • Voltage/Current /Power status levels
  • Simple start /stop operation
  • History of events

Critical Load Cabinet (CLC)
  • Critical Load CabinetIndependent Static Bypass Switch Circuit within each UPS module
  • Independent Parallel and Static Bypass Control Circuitry within each UPS module
  • Elimination of common control single points of failure
  • System Maintenance Bypass Circuit with Electrical Mechanical Interlocks as standard
  • UPS MMS monitoring system

CLC Monitoring System Features
  • Monitors complete UPS Multi-Module System
  • Utilizes Ethernet and 10BaseT
  • Touch screen operator terminal
  • MMS mimic flow diagram and color status display
  • MMS UPS module metering
  • System Voltage/Current /Power

Measurement displays
  • Individual UPS module and battery data screen
  • System event and alarm screens
  • Alarm history screens
  • Remote web monitoring
  • Trend data screens
  • Operator function screens
  • High communication capability


UPS Module KVA Capacity
100, 150, 225, 300, 375, 500 and 750kVA Modules

Standard Features
  • UL1778 / cUL, UL891 approved
  • IGBT
  • Conformally coated boards (industrial environment)
  • Front access only (serviceability)
  • DiamondSense battery self-test

MMS Features
  • Parallel redundant or capacity system configuration
  • MMS Capacity: Up to 8 UPS modules in parallel
  • nstantaneous equal load sharing
  • Individual UPS modules can be removed from an on-line system for maintenance.
    (Note: redundancy will be lost)
  • System maintenance bypass as standard
  • System load bank test circuit (optional)
  • System flexibility
  • Central system monitoring system Battery DC Link 480V DC

Operating Environment
  • Low acoustic noise
  • Temperature: 0~40C
  • Relative humidity: 5~95% (non-condensing)
  • Altitude: 0-9,000 feet (no derating)
  • AC Input Rating
  • -15%~ +15%
  • Power: Rated kVA at 1:1.1 ratio
  • 480 VAC (600 VAC using input transformer)
  •  THD (reflected current): 6% typical (100% load) 9% typical (50% load)
  • 3-phase, 4-wire, plus ground (Bypass: 4-wire, Rectifier: 3-wire)
  • Frequency: 60Hz (±5%)
  • Surge withstand: Meets IEEE C62.41-1991

AC Output Rating
  • 480Y/ 277 VAC or 600Y/ 347 VAC
  • 3-phase, 4-wire, plus ground
  • Output power factor rating: (100-225kVA) 0.8~1.0 Lag (within output kW rating) (300-750kVA) 0.9~1.0 Lag (within output kW rating)
  • Frequency: 60Hz (±0.05%) (free running)
  • Voltage accuracy: ±1%
  • Transient recovery time: Less than 20 ms
  • Load unbalance: 100% ±1% or less
  • Step load change: 0~100% ±2%
  • Load / Return of AC power: ±1% (at 100% load)
  • UPS load transfer, bypass: 5% (at 100% load)
  • THD (voltage): 2% (100% linear load); 5% (100% non-linear load)

One-Line Diagram
One-Line Diagram

Specifications
Specifications
Specifications
Specifications
 