Power Systems Specialists, Inc.
Call Toll Free (888) 305-1555

APC Mitsubishi Toshiba Chloride Datron
UPS Systems 9700 Series
Mitsubishi’s 9700 Series Uninterruptible Power Supply 100 – 225kVA

Mitsubishi 9700 UPSDownload a spec sheet 9700 Brochure (.pdf)



Full IGBT Transistors - Excellent Performance Characteristics

Mitsubishi Electric is the leading manufacturer of Insulated Gate Bipolar Transistors (IGBT). Mitsubishi Electric utilizes IGBTs in the rectifier and inverter sections of our 9700 Series UPS systems. These advanced high performance transistors, provide a variety of intelligent features:

  • High Ampacity Transistors (600A)
  • High Speed Switching
  • Low Control Power

Low Input Current Harmonics (THD)
  • 3% maximum (100% load)
  • 4% maximum (75% load)
  • 5% maximum (50% load) (No additional filtering required)

Input Power Factor
  • 0.99 typical (0~100%)
  • 1:1 Ratio (No oversizing of generator)

Benefit of Lower Input Current
Smaller upstream components (Transformers, Circuit Breakers and cable sizing)

Low Heat Loss / High Efficiency
Use of IGBTs transistor enables efficient high-speed switching (6kHz), thus reducing heat dissipation in the UPS. (Higher efficiency means lower cost per kilowatt to the customer.)

Isolated Redundant System

The 9700 Series is designed for isolated redundant applications.

  • Lower cost to consumer, small footprint, less components.
  • Different kVA sizes and different series can be used for greater flexibility of the overall system.

Extended Battery Life (0-100% Load Step)
Supplemental current from the batteries is no longer required with the installation of IGBTs transistor in both the converter and inverter. Other UPS systems require assistance from the battery during step load conditions. The additional battery cycling results in decreased battery life.

Superior Functions
  • Automatic restart
  • Automatic retransfer
  • Converter walk-in function
  • Battery monitoring
  • Ripple-free DC output (rectifier)
  • 1-set "Form A" dry contracts of selectable items
  • Large overload / overcurrent capacity
  • Battery temperature compensation
  • Adjustable DC cut-off

Operator-Friendly Control Panel LCD Monitor Displays
  • Mimic bus diagram
  • Operator control station
  • Touch panel input
  • System metering
  • History of events
  • Trend graph
  • Menu-driven start-up procedures
  • Menu-driven operating procedures

Additional Features
  • Password locked for start / stop operation
  • Sealed EPO button Realtime Battery Monitoring
  • Remaining time in batterycharge displayed for operator
  • Software algorithms continuously calculate and update actual remaining time in battery charge.

LCD monitor displays
  • System metering
  • Menu-driven start-up procedures
  • Menu-driven operation procedures
  • History of events
  • Trend graph

Quiet Operation
  • 100kVA 63dB (A scale, 1m)
  • 150 - 225kVA 65dB (A scale, 1m)

Software
  • RS-232C parallel interface
  • Multiple server shutdown software (V. 1.50)
  • DiamondLink application software
  • 90% of all operating systems are compatible with DiamondLink
  • Multilingual
  • Paging, E-mail capability during power events
  • Auto-dial
  • Ethernet LAN connection interface (optional)
  • SNMP Interface

Warranty
Standard warranty is two years, including parts and labor.
(NOTE: All information subject to change without prior notice.)

GSA Contract Number
GS-07F-9526G

One-Line Diagram
One Line Diagram

UPS Monitoring Equipment & Software

Diamond LinkDiamondLink is an advanced, user-customizable power monitoring, management, and shutdown software designed to provide information about the power conditions of the UPS system. DiamondLink will monitor the health and status of your UPS system and, when critical events occur, will notify you and perform a graceful, unattended shutdown.


DiamondLink can be configured to perform appropriate actions when an event is detected. The user configurable actions include:

  • Broadcasting – Send event messaging to managers on your system
  • E-mail – Send e-mails or pages as events occur with your UPS system
  • SNMP Messaging – Send SNMP messaging to NMS managers
  • Operating System Shutdown – Shutdown your servers when power is running low

The NetCom hardware SNMP/Web adapter runs an embedded Simple Network Management Protocol (SNMP) software agent. This powerful and intelligent unit is designed for the rigorous task of managing the UPS systems that protect equipment and the critical data residing throughout the network. The NetCom features:

Remote UPS status monitoring –
Monitor a remote UPS system using an RS-232 Cable to the NetCom for one UPS system to a remote workstation (NMS) through an Ethernet connection

  • Web Card – Assign an IP address to your UPS system to monitor and control the UPS system from anywhere around the world
  • SNMP Adapter – Turn the UPS system’s protocol into an SNMP software agent and enable SNMP traps
  • SNMP Viewer – Unique Mitsubishi design that color coordinates SNMP messages that inform the NMS about all current UPS alarms
  • Send Shutdown Signal to Networked Servers – Send a shutdown signal to servers connected via the Ethernet network
  • Battery and Service Monitoring – Monitor the battery life and servicing details of the UPS
  • E-mail – Send the Administrator an e-mail when an event occurs ModBus Communications for Building Management Systems

The MUCM card allows the customer to integrate Mitsubishi Electric UPS systems into their current Building Management Solution. The MUCM is a user-programmable protocol converter, or data concentrator, that is DIN-rail mountable, with 2 serial ports: One RS-232, one RS-485, and over 2,048 internal mailbox registers. Through the ModBus protocol converter, the UPS system’s variables can be monitored through various Building Management System vendors’ software.


Operation Menu
Operation Menu

Dimensions
Cabinets
Battery Cabinets

Standard Features
  • IGBTs transistor (converter/ inverter)
  • UL/cUL approved (1778)
  • Hermetically sealed boards (industrial environment)
  • Front access only (serviceability)

Battery DC Link
  • 360 VDC

Operating Environment
  • Low acoustic noise
  • Temperature: 0~40°C
  • Relative humidity: 5~95% (non-condensing)

AC Input Rating
  • +10%~-15%
  • 208 VAC
  • THD: 3% max. (100% load)
  • 3-phase, 3-wire, plus ground
  • Frequency: 60Hz (±5%)
  • Surge withstand: meets IEEE 587/ANSI C62.41
  • Input THD: 3% max. (100% load) 5% max. (50% load)

AC Output Rating
  • 3-phase, 4-wire
  • Output power factor rating: 0.8
  • Frequency: 60Hz
  • Voltage accuracy: ±1%
  • Transient recovery time: 20ms
  • Load unbalance: 100% ±1% or less
  • Step load change: 0~100% ±2%
  • Load/Return of AC power: ±1%
  • UPS load transfer, bypass: ±5%
  • THD:2% max.(100% linear load); 5% max.(100% nonlinear load)
  • Slew rate: Adjustable
  • Adjustable Output Voltage ±5%
 

Home | Power Quality Products | Power Quality Services