Mitsubishi’s 2033D Series Uninterruptible Power Supply 30/50/80kVA

Mitsubishi 2033d UPSDownload a spec sheet 2033D Brochure (.pdf)

Full IGBT Transistors - Excellent Performance Characteristics

Mitsubishi Electric is the leading manufacturer of Insulated Gate Bipolar Transistors (IGBTs), and now utilizes IGBTs in the converters and inverters of its 2033D Series UPS systems. These advanced, high-performance transistors provide a variety of intelligent features.

  • High Ampacity Transistors
  • High Speed Switching
  • Low Control Power

Low Input Current Harmonics (THD)
  • 4% (100% load)
  • 5% (75% load)
  • 7% (50% load)
  • (No additional filtering required)

Generator Sizing Ratio (UPS)
  • 1:1 (UPS kVA/Generator kW)

Low Heat Loss / High Efficiency
TransistorUse of Intelligent Power Module transistors enables efficient high-speed switching (8kHz), thus reducing heat dissipation in the UPS. (Higher efficiency means lower cost per kilowatt to the customer.)

Internal Maintenance Bypass
All 2033D Series UPS systems are equipped with an internal wrap around maintenance bypass system for greater maintenance flexibility. UL1778 approved.

Superior Functions
  • Multi-module Systems: 2X system for redundancy only
  • Automatic restart after low battery inverter stop
  • Automatic retransfer
  • Rectifier walk-in function
  • 2 sets of "Form C" dry contacts of selectable items
  • High tolerance for overload /overcurrent
  • Battery monitoring
  • Battery temperature compensation
  • Line Drop compensation

Extended Battery Life
Current source from batteries for step loads is no longer required with the installation of Intelligent Power Module transistors in both the converter and the inverter. Previous UPS systems required assistance from batteries when the converter was unable to supply the required current. This cycling of batteries caused shorter life.

Mitsubishi Electric Intelligent Power Modules incorporate the latest technologies and provide step load applications (0-100%) without the use of batteries, thus ensuring maximum battery service life (i.e., lower lifetime cost of UPS system).


Internal Maintenance Bypass
All 2033D Series UPS systems are equipped with an internal wrap around maintenance bypass system for greater maintenance flexibility.
  • UL 1778 approved

Superior Control
All 2033D Series UPS systems use pulse width modulation (PWM) for superior control and performance. A digital signal processor (DSP) ensures precise control of all input / output parameters.

Operator-Friendly Control Panel Features
  • Mimic bus diagram
  • Operator control station
  • Touch panel input

LCD Monitor Displays
  • Measurement MenuSystem metering
  • Menu-driven start-up procedures
  • Menu-driven operating procedures
  • History of events
  • Load true power factor

Additional Features
  • Password lock out for start / stop operation
  • EPO button

Real-Time Battery Monitoring
  • Remaining battery time displayed for operator
  • Integrated "DiamondSense" system automatically detects weak cells

Superior Functions
  • Automatic restart
  • Automatic retransfer
  • Converter walk-in function
  • Battery monitoring
  • Ripple-free DC output (converter)
  • 2 sets "Form C" dry contacts of selectable items
  • Large overload / overcurrent capacity
  • Battery temperature compensation
  • Adjustable DC cut-off
  • Line drop compensation

Quiet Operation
  • 65dB (A scale, 1m)

Software
  • RS232C serial interface
  • DiamondLink application software
  • 90% of all operating systems are compatible with DiamondLink
  • Multilingual
  • Paging, E-mail capability during power events
  • Auto-dial
  • Multiple server shutdown capabilities

Warranty
Standard warranty is two years, including parts and labor.
(NOTE: All information subject to change without prior notice.)

GSA Contract Number
GS-07F-9526G

UPS Monitoring Equipment & Software

Diamond LinkDiamondLink is an advanced, user-customizable power monitoring, management, and shutdown software designed to provide information about the power conditions of the UPS system. DiamondLink will monitor the health and status of your UPS system and, when critical events occur, will notify you and perform a graceful, unattended shutdown.


DiamondLink can be configured to perform appropriate actions when an event is detected. The user configurable actions include:

  • Broadcasting – Send event messaging to managers on your system
  • E-mail – Send e-mails or pages as events occur with your UPS system
  • SNMP Messaging – Send SNMP messaging to NMS managers
  • Operating System Shutdown – Shutdown your servers when power is running low

The NetCom hardware SNMP/Web adapter runs an embedded Simple Network Management Protocol (SNMP) software agent. This powerful and intelligent unit is designed for the rigorous task of managing the UPS systems that protect equipment and the critical data residing throughout the network. The NetCom features:

Remote UPS status monitoring –
Monitor a remote UPS system using an RS-232 Cable to the NetCom for one UPS system to a remote workstation (NMS) through an Ethernet connection

  • Web Card – Assign an IP address to your UPS system to monitor and control the UPS system from anywhere around the world
  • SNMP Adapter – Turn the UPS system’s protocol into an SNMP software agent and enable SNMP traps
  • SNMP Viewer – Unique Mitsubishi design that color coordinates SNMP messages that inform the NMS about all current UPS alarms
  • Send Shutdown Signal to Networked Servers – Send a shutdown signal to servers connected via the Ethernet network
  • Battery and Service Monitoring – Monitor the battery life and servicing details of the UPS
  • E-mail – Send the Administrator an e-mail when an event occurs ModBus Communications for Building Management Systems

The MUCM card allows the customer to integrate Mitsubishi Electric UPS systems into their current Building Management Solution. The MUCM is a user-programmable protocol converter, or data concentrator, that is DIN-rail mountable, with 2 serial ports: One RS-232, one RS-485, and over 2,048 internal mailbox registers. Through the ModBus protocol converter, the UPS system’s variables can be monitored through various Building Management System vendors’ software.


One Line Diagrams/Single Module Systems
SMS1 - Single Module System
One Line Diagram

SMS2 - Single Module System with External MBS 480V in/480V out
One Line Diagram

SMS3 - Single Module System with External MBS 480V in/208V out
One Line Diagram

One Line Diagram

2033D One Line Diagrams/Multi-Module Systems
MMS1 - Multi-Module System
One Line Diagram

MMS2 - Multi-Module System with External MBS 480V in/480V out
One Line Diagram

MMS3 - Multi-Module System with External MBS 480V in/208V out
One Line Diagram

Dimensions/Weights/Specifications

Standard Features
  • IGBT transistors (converter / inverter)
  • UL / cUL approved (1778)
  • Zero energy MBS
  • Conformal coated boards (industrial environment)
  • Front access (serviceability)

Battery DC Link
  • 480 VDC

Cable Entry
  • Bottom (Standard)
  • Top (Optional)

Operating Environment
  • Low acoustic noise
  • Temperature: 32~104°F
  • Relative humidity: 5~95% (non-condensing)
  • Altitude: 9,000 ft

AC Input Rating
  • +15%~ −30% at derating load
  • Power: Rated kVA at 1:1 ratio
  • Power Factor: 0.98 (100% load) 0.97 (50% load)
  • 208 / 480 / 600 VAC
  • THD: 4% typ. (100% load) 7% typ. (50% load)
  • 3-phase, 3-wire, plus ground
  • Frequency: 45.4Hz to 65Hz
  • Surge withstand: Meets IEEE 587/ANSI C62.41

AC Output Rating
  • 3-phase, 4-wire
  • 208/480 VAC
  • Frequency: 60Hz
  • Voltage accuracy: ±1%
  • Transient recovery time: 16.6 ms
  • Load unbalance: 100% ±2% or less
  • 100% Step load change: 0~100% ±3%
  • Loss/ Return of AC power: ±1%
  • UPS load transfer, bypass: ±3%
  • THD: 2% (100% linear load) 5% (100% non-linear load)

Slew rate: Adjustable
  • Crest Factor 3:1
 