| MODEL |
GEN-1K |
GEN-1.5K |
GEN-2K |
GEN-3K |
| RATED POWER |
1kVA/700W |
1.5kVA/1.05kW |
2kVA/1.4kW |
3kVA/2.1kW |
| INPUT CABLE |
L5-15P |
L5-20P |
L5-20P |
L5-30P |
| VOLTAGE |
60
- 138VAC, (120VAC) |
| FREQUENCY |
50Hz
/ 60Hz (+/-8% |
| POWER FACTOR |
>0.95 |
>0.97 |
| OUTPUT RECEPTACLES |
(4) 5-15R |
(3) 5-15R + Terminal Block |
| VOLTAGE |
110V/115V/120V (Factory set 110V) |
| FREQUENCY |
50Hz / 60Hz (auto tracking) |
| VOLTAGE REGULATION |
+ / -2% |
| DISTORTION |
<
3 % (Linear load) |
<
4% (Full linear load) |
| WAVEFORM |
Pure
sinewave |
| OVERLOAD CAPACITY |
105%-150% load 30
sec., > 150% load for 200ms |
| FAX/Modem surge protection |
RJ11 connector |
| BATTERY VOLTAGE |
36V/3×7AH |
48V/4×7AH |
96V/8×7AH |
96V/8×7AH |
| TYPE |
Maintenance free sealed
lead-acid |
| BACK-UP TIME |
FULL LOAD |
5 min. |
5 min. |
9 min. |
5 min. |
| HALF LOAD |
14 min. |
14 min. |
21 min. |
17 min. |
|
| ON - LINE OPERATION |
Zero break at input line
loss and recovery |
| INDICATOR |
Load status,
Battery status, UPS Operation status |
| AUDIBLE ALARM |
DC
mode : every 4 seconds |
UPS
Abnormal : continuing |
| NOISE LEVEL |
<
45 dBA (at 1 meter) |
<
50 dBA (at 1 meter) |
| COMMUNICATION INTERFACE |
RS-232 standard, RJ45 I/O port and AS400 contact relay optional |
| TEMPERATURE |
32
F to 104F (0C TO 40C) |
| HUMIDITY |
0%
to 90%(non-condensing) |
| WEIGHT/ NET (lbs) |
31 |
41 |
78 |
78 |
| DIMENSIONS (W×D×H) inches |
5.7×15.7×8.7 |
5.7×18.5×8.7 |
7.5×17.7×14.2 |
7.5×17.7×14.2 |