Power Systems Specialists, Inc.
Call Toll Free (888) 305-1555

APC Mitsubishi Toshiba Chloride Datron
UPS Systems Chloride
EDP90RT (Single Module) True Double Conversion UPS

EDP90Designed with the most secure architecture for use under extreme power supply conditions. Double conversion technology ensures maximum output isolation to power related network disturbances. The EDP90 is a reliable UPS, easy to install, control and use.

  • 3-Phase UPS
  • True On-line Double Conversion Protection
  • Transistorized PWM Inverter
  • State-of-the-Art Communications
  • Advanced Battery Management
  • Extended Battery Options
  • Internal Maintenance Bypass
  • User Friendly, Multilingual Display
  • Dual RS232
  • AS400
  • Parallel up to six modules

Download a spec sheet Download a spec sheet

Model 300 Performance Specs
   4x4    4x4    4x4  
 kVA/kW @ .8 PF    225/180    250/200    300/240  
 Input Voltage    480Y/277    480Y/277    480Y/277  
 Output Voltage    480Y/277    480Y/277    480Y/277  
 Frequency    60 Hz    60 Hz    60 Hz  
 Nominal Input Current    287    319    383  
 Maximum Input Current    359    399    478  
 Nominal Output Current    271    301    361  
 System Efficiency 100%    92    92    92  
 Full Load Heat Rejection (BTU/hr)    53,405    59,339    71,207  
 Height    70    70    70  
 Width    96    96    96  
 Depth    33    33    33  
 Weight    4,500    4,500    4,500  

Model 400 Performance Specs
   4x4  4x4  4x4
 kVA/kW @ .8 PF    300/240    350/280    400/320  
 Input Voltage    480Y/277    480Y/277    480Y/277  
 Output Voltage    480Y/277    480Y/277    480Y/277  
 Frequency    60 Hz    60 Hz    60 Hz  
 Nominal Input Current    383    446    510  
 Maximum Input Current    478    558    638  
 Nominal Output Current    361    421    481  
 System Efficiency 100%    92    92    92  
 Full Load Heat Rejection (BTU/hr)    71,207    83,075    94,943  
 Height    70    70    70  
 Width    96    96    96  
 Depth    33    33    33  
 Weight    5,410    5,410    5,410  

Model 500 Performance Specs
   4x4  4x4  4x4
 kVA/kW @ .8 PF    400/320    450/360    500/400  
 Input Voltage    480Y/277    480Y/277    480Y/277  
 Output Voltage    480Y/277    480Y/277    480Y/277  
 Frequency    60 Hz    60 Hz    60 Hz  
 Nominal Input Current    510    574    638  
 Maximum Input Current    638    717    797  
 Nominal Output Current    481    541    601  
 System Efficiency 100%    92    92    92  
 Full Load Heat Rejection (BTU/hr)    94,943    106,810    118,678  
 Height    70    70    70  
 Width    127    127    127  
 Depth    33    33    33  
 Weight    6,685    6,685    6,685  

Battery Data
 225 kVA  250 kVA  300 kVA  350 kVA  400 kVA  450 kVA  500 kVA  Cabinets  
 Pack 123  7    5    -    -    -    -    -    2 x C  
 Pack 115  10    8    5    -    -    -    -    2 x C  
 Pack 125  13    11    8    5    -    -    -    2 x D  
 Pack 126  14    12    9    6    -    -    -    3 x C  
 Pack 133  18    15    12    9    4    -    -    2 x BC5  
 Pack 127  19    16    13    9    7    5    -    3 x C  
 Pack 128  24    20    16    13    10    8    6    3 x D  
 Pack 134  23    19    14    12    9    7    5    4 x C  
 Pack 135  29    25    19    15    13    10    8    4 x C  
 Pack 136  35    30    22    17    14    12    9    3 x BC5  
 Pack 137  35    31    24    19    16    13    11    4 x D  
 Pack 138  52    45    35    27    21    18    15    4 x BC5  

Cabinet type C dimensions: 33.0” W x 33.0” D x 70.0” H
Cabinet type D dimensions: 40.0” W x 33.0” D x 70.0” H
Cabinet Type BC5 dimensions: 42.0” W x 32.0” D x 75.0” H
 

Home | Power Quality Products | Power Quality Services