The EDP70Pus is a tested and reliable design offering high quality protection to a broad spectrum of critical loads. The EDP70Plus UPS is essential for mission-critical applications such as data centers, servers, industrial applications and management systems.
Features Include:
• True On-line Protection
• IGBT PWM Inverter
• State-of-the-Art Communications
Solutions
• Input/Output Circuit
• Advanced Battery Management
• Internal Maintenance
• User Friendly, Multilingual
• Dual RS232 Ports
• Field Upgradeability
Download a spec sheet
| Performance and Physical Data (Nominal Conditions with Linear Load) |
| Model 24 - 12 kVA |
|
2x2 |
4x2 |
4x4 |
| kVA/kW @ .67 PF |
12/8 |
12/8 |
12/8 |
| Input Voltage |
208Y/120 |
480 |
480 |
| Output Voltage |
208Y/120 |
208Y/120 |
480Y/277 |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
| Nominal Input Current |
37 |
16 |
16 |
| Maximum Input Current |
42 |
19 |
19 |
| Nominal Output Current |
33 |
33 |
14 |
| System Efficiency 100% |
88 |
87 |
86 |
| Full Load Heat Rejection (BTU/hr) |
3,750 |
4,150 |
4,550 |
| Height |
56.0 |
56.0 |
56.0 |
| Width |
27.5 |
27.5 |
27.5 |
| Depth |
28.7 |
28.7 |
28.7 |
| Weight |
900 |
1200 |
1400 |
|
| Model 24 - 18 kVA |
|
2x2 |
4x2 |
4x4 |
| kVA/kW @ .67 PF |
18/12 |
18/12 |
18/12 |
| Input Voltage |
208Y/120 |
480 |
480 |
| Output Voltage |
208Y/120 |
208Y/120 |
480Y/277 |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
| Nominal Input Current |
57 |
25 |
25 |
| Maximum Input Current |
60 |
26 |
26 |
| Nominal Output Current |
50 |
50 |
22 |
| System Efficiency 100% |
88 |
87 |
86 |
| Full Load Heat Rejection (BTU/hr) |
5,460 |
6,200 |
6,600 |
| Height |
56.0 |
56.0 |
56.0 |
| Width |
27.5 |
27.5 |
27.5 |
| Depth |
28.7 |
28.7 |
28.7 |
| Weight |
900 |
1200 |
1400 |
|
| Model 24 - 24 kVA |
|
2x2 |
4x2 |
4x4 |
| kVA/kW @ .67 PF |
24/16 |
24/16 |
24/16 |
| Input Voltage |
208Y/120 |
480 |
480 |
| Output Voltage |
208Y/120 |
208Y/120 |
480Y/277 |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
| Nominal Input Current |
76 |
33 |
33 |
| Maximum Input Current |
78 |
34 |
34 |
| Nominal Output Current |
67 |
67 |
29 |
| System Efficiency 100% |
88 |
87 |
86 |
| Full Load Heat Rejection (BTU/hr) |
6,800 |
7,500 |
8,200 |
| Height |
56.0 |
56.0 |
56.0 |
| Width |
27.5 |
27.5 |
27.5 |
| Depth |
28.7 |
28.7 |
28.7 |
| Weight |
900 |
1200 |
1400 |
|
|
| Battery Data |
|
24 - 12 kVA |
24 - 18 kVA |
24 - 24 kVA |
Cabinets |
| Pack 106 |
47 |
28 |
17 |
Internal* |
| Pack 107 |
47 |
28 |
17 |
1 x A |
| Pack 108 |
76 |
45 |
27 |
1 x A |
| Pack 109 |
116 |
72 |
40 |
1 x B |
| Pack 131 |
124 |
97 |
71 |
1 x B |
|
|
|
|
|
Cabinet type A dimensions: 17.8” W x 28.7” D x 56.0” H
Cabinet type B dimensions: 33.6” W x 28.7” D x 56.0” H |
|